D series high-frequency online UPS 6~20kVA

Product profile

Digital Series (parallel redundancy) UPS D6KS ~ 3 D 20 KS with double conversion pure online architecture, the architecture can block the impact of abnormal power on the load, at the same time also can guarantee the stable and reliable output, let the safety of the load, is the best can effectively solve the problem of all power architecture design, using digital control technology (DSP / MCU chip), can choose the function of parallel expansion and parallel redundancy, provide the user with power planning elasticity and more secure guarantee.


Basic Features

Smaller design

The application of advanced control technology, greatly improve the power factor, small volume, light weight.


Online maintenance design (optional)

If you select the maintenance switch, you can safely carry out online maintenance under the condition of continuous load power supply as long as you turn the UPS to the maintenance mode; If you plan for N+1 parallel redundancy, even if the mains power is interrupted during maintenance, your valuable equipment can get uninterrupted high-quality power supply.


Comprehensive functional design

DC start function enables you to use UPS without mains power supply. The function of timing on/off and remote monitoring can realize the goal of unmanned. The powerful charging function is convenient for you to extend the standby time. The intelligent charging mode extends the battery life and saves

money. The automatic restart function makes it unnecessary for you to turn on the UPS in person after the standby UPS is turned off. Comprehensive functional design brings more convenience to your work.


Excellent technical indicators

The input power factor close to 1 greatly reduces the pollution to the municipal power grid, improves the utilization of the grid, and is a real green power source. The ultra wide input voltage range provides the most complete protection for your valuable equipment under various harsh power environments.

Nearly 93% full load operation efficiency, effectively saving your electricity bill. Strong anti-interference ability, meeting the requirements of IEC61000-4 for electromagnetic interference, can effectively eliminate noise, high voltage and breakthrough on the power grid, and provide a clean power environment for your

equipment.

image.png


Optional lightning protection function

It can be equipped with Class D lightning arrester with surge and lightning protection design to effectively protect equipment from lightning interference.


High-reliability and parallel capacity expansion technology (optional)

You only need to consider your actual power needs and plan an appropriate UPS. In the future, if you need corresponding power expansion due to equipment expansion, you only need to purchase the expanded UPS and connect it to the original power system in parallel, which increases the flexibility of planning and greatly reduces the waste of investment.?


N + X parallel redundancy function (optional)

The N+X parallel redundancy function means that there is one more UPS at any time to guarantee your important equipment. When planning the power supply system, add one more than the rated capacity. In this way, when any UPS in the system fails, the additional UPS will enable the power supply system to continuously provide high-quality power for your important equipment, making the system more reliable. At the same time, the advanced current sharing technology enables each UPS in parallel operation to share the load current equally. While improving the system reliability, It also extends the service life of UPS.


Intelligent power supply monitoring and management software: UPSILON 2000

Support Microsoft Windows95/98/Me/NT/2000/XP/Linux operating system, applicable to TCP/IP LAN, and support TCP/IP network monitoring UPS; Provide hierarchical directory structure management network UPS; Abnormal event notification; Automatically detect UPS model and communication port; Provide password protection; UPS can be switched on/off regularly; Support UPS timing self-test function; Support graphic real-time display of UPS status; Support network shutdown of servers and workstations; Support closing most applications and saving related documents; Support multi language and English platforms; Support online help function. It has the function of data recording (including mains power, UPS, load, battery) and event log, which is convenient for the system administrator to carry out daily UPS maintenance.?


Complete monitoring and communication function?

RS-232, intelligent slot (Intelligent Slot) and other monitoring and communication interfaces are provided. Users can realize centralized monitoring and remote monitoring functions through the SNMP network card.


Technical Specifications

? ? ?? ? ? ? ? Model

D6K

D6KS

D10K

D10KS

3D10KS

3D15KS

3D20KS

Rated capacity (PF=0.9)

6kVA/5.4kW

10kVA/9kW

15kVA/13.5kW

20kVA/18kW

Input

Input distribution line

Single-phase second-line+ground line

Three-phase, four-wire+ground wire

Voltage

120VAC~300VAC

150VAC~500VAC

Frequency

50/60Hz±10%

Output

Voltage

220/230±1%VAC

Frequency

Synchronizing with the input (mains mode)

50/60Hz±0.5% (battery mode)

Load peak?

ratio

3:1?(max)

Discharge waveform

Pure sine wave

Transfer time

Zero interruption

Built-in battery (12V)

7Ah/9Ah×16

-

7Ah/9Ah×16

-

-

External battery DC voltage nominal

-

192Vdc

-

192Vdc

192/240Vdc

Battery type

Valve-controlled lead-acid maintenance-free storage battery

Overload capacity

105% -120%, to?bypass?after?10 seconds;
120-140%,?to?bypass?after?200ms;
? ?140-150%,?to?bypass?after?200ms, and then?shutdown?10 seconds later;
? > 150% shutdown?immediately

Distortion rate (full load)

<3% (linear load)

<5% (nonlinear load)

Communication function

Rs-232 interface (optional USB interface)+SNMP smart slot

Working temperature

0℃~40℃

Relative humidity

0~90% (no condensation)

Dimension(D×W×H) mm

515×248×616

515×240×460

515×248×616

515×240x460

540×190x340

560×240×530

Weight (kg)

57/64

17.5

60/67

19.5

15.5

28.5

28.5

Compliancewithstandards

?GB/T14715-2017; YD/T1095-2018; EN62040-1:2008+A1:2013; EN62040-2:2018

1. Optional rated capacity (output power) PF = 0.8.

2. The model with "S" is a extended time model, and the battery should be configured according to the external battery DC voltage according to the battery life time.

3. Load in high altitude = rated power x reduction coefficient

Altitude (m)

1000

1500

2000

2500

3000

3500

4000

4500

5000

Frequency reduction coefficient

100%

95%

91%

86%

82%

78%

74%

70%

67%

?If the UPS is used above 1000m, the decreasing rated output must be used, as shown in the table above.

* The above parameters may be adjusted and changed, please refer to the physical object.


主站蜘蛛池模板: 一本之道无吗一二三区| 再深点灬舒服灬太大了一进一出| 俺去啦在线视频| **肉体一级毛片| 天天躁夜夜躁狠狠躁2021西西| 亚洲国产精品一区二区久| 隔壁女邻居在线观看| 女人双腿搬开让男人桶| 中日韩欧美经典电影大全免费看| 狠狠综合久久久久综合小说网| 国产91无套剧情在线播放| 91手机看片国产永久免费| 日本精品一区二区三区视频| 日本边添边摸边做边爱的视频| 四虎影片国产精品8848| 黑料不打烊tttzzz网址入口| 手机看片1024旧版| 亚洲欧美日韩国产vr在线观| 精品久久久久久无码人妻蜜桃| 性xxxx黑人与亚洲| 卡通动漫精品一区二区三区| 97人洗澡从澡人人爽人人模| 日本中文字幕有码在线视频| 天天躁日日躁狠狠躁欧美老妇 | 久久亚洲精品中文字幕| 精品国产一区二区三区久久 | 乱爱性全过程免费视频| 看一级毛片女人洗澡| 国产日本在线视频| 全免费毛片在线播放| 一本色道久久88加勒比—综合| 日本妇乱子伦视频| 亚洲欧美日韩国产精品网| 男男动漫全程肉无删减彩漫| 啊灬啊别停灬用力啊老师在线| 你懂的在线播放| 成人免费播放视频777777| 亚洲av无码欧洲av无码网站| 精品一区二区久久久久久久网精| 国产日产久久高清欧美一区| 全免费毛片在线播放|