D series (3Phase), high frequency online UPS 20 ~ 180 kVA (tower/ rack type)

Product profile

Digital Series high frequency UPS power supply, equipped with dual DSP controller, rectifier, inverter, charge and discharge are controlled by DSP digital, power module independent flow control, no single point fault risk, integrated the latest power electronics advanced technology. The innovative design provides this series with unparalleled reliability and high performance. Very high input power factor and very low input current distortion rate ensure the green and environmental protection of the product, and the high efficiency of the whole machine ensures the energy saving of the product. This series of products can be run by 8 machines.


Basic Features

1. 3 phase input, 3 phase output pure online dual conversion products, support 380 / 400 / 415V, 50 / 60Hz power grid system, to provide the best power quality and load protection.

2. Super load adaptability, super overload and short circuit capacity.

3. Ultra-wide input voltage and frequency range, adapt to the harsh power grid environment, adapt to the use of various fuel generators.

4. The input power factor is up to 0.99, the input harmonic current is less than 3%, and the overall efficiency is greater than 95%. Green, high efficiency and energy saving.

5. DSP full digital control realizes full digital control of power conversion links such as rectification, inversion and charge and discharge.

6. Digital cycle control technology, high reliability.

7. Intelligent battery management scheme to prolong the battery life.

8. The system adopts a modular design, with a stable and reliable performance.

9. All the fans in the system are redundant in design, which greatly improves the reliability of the system.

10.The EPO emergency shutdown function can be realized.

11.Ultra-long average failure-free time (>200,000 hours) and ultra-low average maintenance time (<0.5 hours).

12.Rich accessories: dust net, SNMP network communication card, lightning protection module, battery temperature compensator, mobile phone SMS alarm.

13.All circuit boards adopt three-proof technology.

14.Traditional modular UPS can be replaced by parallel, saving the high cost of modular cabinet.

15.real color touch screen (rack type LCD display Or touch screen optional) enables users to more intuitively understand the working state and operating parameters of UPS, such as input and output voltage and frequency, load size, battery capacity, machine temperature, etc., so that all operations are clear at a glance.


Technical Specifications


Capacity

20/30/40kVA

60/80kVA

100/120kVA

160/180kVA

Import

Input mode

Three-phase, ? four-wire+grounding

Rated voltage

380/400/415Vac

Voltage range

138 to 485Vac; 305 to 485Vac, 138 to 305 Vac

Frequency range

40~70Hz

Power factor

≥0.99

Input current harmonics

3% (100% nonlinear load)

Bypass range

Upper limit of bypass protection voltage: 220V: +25% (optional +10%, +15%, +20%);
? 230V: +20% (optional +10%, +15%);
? 240V: +15% (optional +10%)

Lower pass protection voltage limit: -45% (optional-10%, -20%, -30%)

Bypass frequency protection range: ±10%

Output

Output method

Three-phase, four-wire+grounding

Rated voltage

380/400/415Vac

Power factor

0.9

Voltage accuracy

±1%

Output ? frequency

Main ? mode

Synchronized with input; output frequency 50 (1±0.02%) Hz beyond ±10% (±1%, ±2%, ±4%, ±5%)

Battery ? mode

(50/60±0.2%)Hz

Load peak ratio

3:1

Output voltage distortion

2% linear load, and 4% nonlinear load

Battery

Battery voltage

Voltage optional: ±180V/±192V/±204V/±216V/±228V/±240V/±252V/±264V/±276V/±288V/±300V (30/32/34/36/38/40/42/44/46/48/50)

360Vdc~600Vdc(30~50sections optional)

Charging current

15A?max

15A?max

30A?max

45A?max

Transfer time

Municipal mode to bypass mode: 0ms (tracking);?

municipal mode to battery mode: 0ms

Protect

Overload capacity

Load ≤110%, 60mins;125%, 10mins; 150%, 1min; >150%,?shutdown immediately.

Overtemperature ? protection

Normal mode: Switch to the bypass mode;?

Battery mode: Turn off the output ? immediately

Emergency ? Shutdown (EPO)

Cut off the output immediately

Communication interface

USB, RS485, optical coupling node, machine (option), SNMP card (option), Relay ? card (option)

Work ? environment

Working ? temperature

0℃40℃

Relative humidity

0~95% with no condensation

Storage ? temperature

-25℃55℃

Altitude

<1500m, exceed 1500m according to GB/T 3859.2

Physical ? characteristics

?Dimensions (D×W×H)

720×250×530mm(rack type 730×440×130mm)

865×250×860mm

885×440×1200mm

Net weight (Kg)

32/34/35

70/72

155/160

190/199

Operative standard

CE,EN/IEC 62040-2,EN/IEC 62040-1-1,YD/T1095-2018

* The above parameters may be adjusted and changed, please refer to the physical object.


主站蜘蛛池模板: 久久综合欧美成人| 免费的一级毛片| **aaaaa毛片免费| 天天做天天摸天天爽天天爱| 丰满少妇人妻无码| 最新版天堂资源官网| 亚洲日本在线电影| 狠狠色噜噜狠狠狠狠69| 又粗又猛又黄又爽无遮挡| 野花香高清在线观看视频播放免费| 国产福利高颜值在线观看| 91视频一区二区三区| 女人18毛片a级毛片| 两个人看的www日本动漫| 日本护士取精视频xxxxx全部| 亚洲av无码久久忘忧草| 欧美黑人乱大交| 伊人色综合久久天天| 精品国产福利在线观看91啪 | 国产精品一区二区综合| 99久久99久久精品免费观看| 好深好爽办公室做视频| 中文国产成人精品久久不卡| 日日夜夜操视频| 久久国产精品久久久| 暖暖免费高清日本中文| 亚洲丰满熟女一区二区v| 欧美日韩亚洲国内综合网香蕉| 亚洲色成人网一二三区| 皇夫被迫含玉势女尊高h| 动漫美女被羞羞动漫小舞| 老子影院午夜理伦手机| 国产中文字幕免费观看| 高嫁肉柳风车动漫| 国产成人久久精品二区三区 | 亚洲国产另类久久久精品黑人| 毛片a级毛片免费播放下载| 亚洲色成人WWW永久在线观看| 真实的国产乱xxxx| 公交车上性配合享受视频| 精品视频午夜一区二区|